PV Array Combiner Box

Product description

PV array combiner box is mainly applied in medium and large scale surface power station, as the firstly combine device, it is used for the output power of strings combination, DC line protection and parameters monitoring, etc. The product provide reliable guarantee for power station with the characteristic with optimized structural design, strict components selection and reliable fault warning function.

Technical Advantages

 

    Extended DC input voltage range, Max. input open voltage 1000V

    Protection class is IP65 design for outdoor use

    8-16 PV strings can be connected in

    DC fuse and lightning protection module are specially applied for photovoltaic purpose

    Equipped with RSC85 communication interface

    Real-time monitoring functions of operating parameters and status such as array voltage, currenttemperature , etc.

    Modularization design for easy installation and maintainance

Create Value for Our Customers

 With wide DC voltage input range  , accessible to 8 - 16 photovoltaic arrays, a protection class of IP65, a selectable anti-reversion function and string parameter of various groups being monitored, it is the optimal choice for large & medium size ground power stations. 

technical parameter

PDF Download
 

Without anti-reverse Type

Type

Without anti-reverse Without intelligent Type

Without anti-reverse intelligent Type

Model

TH0810/1000-A

TH1610/1000-A

TH0810/1000

TH1610/1000

Electric Parameters

Input Circuit

8-circuit

16-circuit

8-circuit

16-circuit

Input Voltage Range

100V1000V

Max. DC Input VoltageUDCmax

1000V

Max. DC Input Voltage of Single circuit

15A

Max. Input Current after combinationIPVmax

125A

200A

125A

200A

Special Fuse Protection for Each PV String

Yes

Fault Detect for lightning protection  devices

Yes

Device Fault Indication Equipped

DC Overvoltage surge protection

Yes

DC Circuit Breaker level

1000V/160A

1000V/200A

1000V/160A

1000V/200A

Communication Parameters

Communication Interface

RS485

No

RS485 Communication Transmission Distance

9600bps/2km

No

Mechanical Parameters

Weight

23kg

DimensionsW x H x D

820mm×400mm×170mm

Wire Diameter of Input Array

4mm26mm

Wire Diameter of Output

18mm250mm2

50mm270mm2

18mm250mm2

50mm270mm2

Environmental Parameters

Protection Class(conform to EN60529)

IP65

Operating Temperature Range

-30+60

Operating Humidity Range

0%95%

Operating Altitude Range

No derating under 3000mExceed 3000m, derating according to GB/T3859.2

Cooling Method

Natural Cooling

 

Anti-reverse Type

Type

Anti-reverse & Intelligent Type

Anti-reverse & Intelligent Type

Model

TH0810/1000-AD

TH1610/1000-AD

TH0810/1000-D

TH1610/1000-D

Electric Parameters

Input Circuit

8-circuit

16-circuit

8-circuit

16-circuit

Input Voltage Range

100V1000V

Max. DC Input VoltageUDCmax

1000V

Max. DC Input Voltage of Single circuit

15A

Max. Input Current after combinationIPVmax

125A

200A

125A

200A

Special Fuse Protection for Each PV String

Yes

Fault Detect for lightning protection  devices

Yes

Device Fault Indication Equipped

DC Overvoltage surge protection

Yes

Anti-reverse Functions

Yes

DC Circuit Breaker level

1000V/160A

1000V/200A

1000V/160A

1000V/200A

Communication Parameters

Communication Interface

RS485

No

RS485 Communication Transmission Distance

9600bps/2km

No

Mechanical Parameters

Weight

26kg

DimensionsW x H x D

820mm×400mm×230mm

Wire Diameter of Input Array

4mm26mm2

Wire Diameter of Output

18mm250mm2

18mm250mm2

18mm250mm2

18mm250mm2

Environmental Parameters

Protection Class(conform to EN60529)

IP65

Operating Temperature Range

-30+60

Operating Humidity Range

0%95%

Operating Altitude Range

No derating under 3000mExceed 3000m, derating according to GB/T3859.2

Cooling Method

Natural Cooling

 

Close